System Control Units
The core system is available in three distinct configurations:
• 2600HD1
—
The standard system control unit has been desig-
nated the 2600HD1. This model consists of an MB-97 Series
Main Control Board, associated power supply and standard
Protectowire Alarm Point Location Meter. The meter will display
the linear distance in feet or meters from the start of the Detector
p
ortion of the zone to the heat actuated point on the
Protectowire Linear Heat Detector.
• 2600HD2
— A non-metered version of the standard control unit,
model 2600HD2 is available for those applications which do not
require the use of a Protectowire Alarm Point Location Meter.
Should system requirements change after installation, the
2600HD2 has been designed to accommodate easy field installa-
tion of an optional Protectowire Alarm Point Location Meter
without the need to replace the system’s original modules.
• 2600HD3
— The 2600HD3 configuration consists of the
MB-97 Series Main Control Board, associated power supply, and
PCLC based operator interface (OI) touch screen display panel.
This enhanced system control unit provides a Protectowire Alarm
Point Location Meter function with automatic alarm scanning,
data history logging, expanded communication capabilities using
RS232/422/485 serial ports, and when properly configured,
graphic annunciation of the protected hazard area.
System Control Unit Features
Each system control unit contains an MB-97 main board which
provides user operated control switches, complete power
management, adjustable battery charger with monitor, ground fault
detection, lamp test, one Class A/B (Style Z or Y) general alarm
notification appliance circuit, one Class A/B (Style Z or Y) pro-
grammable auxiliary alarm notification appliance circuit and trouble
silence resound timer.
Twelve (12) system status LED indicators are mounted on the
MB-97 main board. A green Power On LED, a red General Alarm
LED, a red Auxiliary Alarm LED, one each yellow Common
Trouble LED, Trouble Silence LED, Ground Fault LED, General
Alarm Circuit Open LED, General Alarm Circuit Short LED,
Auxiliary Alarm Circuit Open LED, Auxiliary Alarm Circuit Short
LED, Battery Out LED and Battery Low LED. On board system
controls consist of four slide switches which activate System Alarm
Test, System Reset, Alarm/Trouble Silence and Lamp Test func-
tions.
All system alarm, trouble, and supervisory indicators are mounted
on the front of the enclosure behind a sealed window, which has
been specially designed to maintain the integrity of the enclosure’s
NEMA rating. In addition, most individ-
ual control and detection modules have
on-board LED indicators which dupli-
c
ate the external LED indicators to assist
in identifying various alarm, trouble or
off normal conditions once the control
panel door has been opened.
The 2600HD Series Control Unit has
been designed to provide maximum
p
ower management flexibility, and is
offered in three standard power configu-
rations. Each configuration is identified
by a unique ordering code which desig-
nates the system’s input operating voltage
and back-up power source:
GC1 — 120 VAC, 50/60 Hz. Input
with Gel Cell (Sealed Lead Acid)
Battery Back-up.
GC2 — 240 VAC, 50/60 Hz. Input with Gel Cell (Sealed Lead
Acid) Battery Back-up.
UC1 — Universal Primary and Back-up Power Input.
Uninterruptible Second Source Back-up Power required.
The UC1 Universal Power Input option utilizes highly efficient
switching power supplies for both system primary and secondary
back-up power input. Each power supply is capable of operating on
input voltage ranges of 120 - 240 VAC or 120 - 250 VDC. In this
configuration, emergency back-up batteries are not used in the
system and the standard MB-97 main board is replaced by the
MB-97-UC1 which does not contain battery charging or monitoring
capabilities. All other functional system controls remain the same.
System Options
Initiating Device Modules – Options A, AA, B, BB, C & CC
The 2600HD Series Control Panel utilizes two distinct input mod-
ules (ZM-2/ZM-3224) for all alarm initiating devices. Both mod-
ules have been designed to operate up to 5,000 feet (1,524m) of
Protectowire Linear Heat Detector as well as other types of initiat-
ing devices such as smoke and flame detectors, water flow switches,
manual pull stations and spot heat detectors.
Options A & AA (Two Class A Detection Zones)
Option A consists of the ZM-2 Input Module configured to pro-
vide two independent Class A (Style D) two wire initiating device
circuits. Each initiating circuit is equipped with one red alarm
LED, one yellow trouble LED and a push button switch for
manual operation of the Protectowire Alarm Point Location
Meter (2600HD1 Systems only). The ZM-2 features program-
mable alarm output signaling, auxiliary alarm and trouble outputs
by zone for operation of other devices such as relays, and on
board cross-zoning circuit for extinguishing applications.
Option AA consists of the ZM-2 plus a special I/O Interface
Module. This option is used only in 2600HD3 Systems.
Options A and AA may not be used with Intrinsic Safety
Barriers (Option G).
Options B & BB (Four Class B Detection Zones)
The ZM-3224 Input Module as utilized in Options B and BB,
provides four independent Class B (Style B) two wire initiating
device circuits. Each initiating circuit is equipped with one red
alarm LED, one yellow trouble LED and a push-button switch
for manual operation of the Protectowire Alarm Point Location
PCLC Graphic Display (2600HD3)
MB-97 Main Board