
8
detectors installed on a 10 foot (3m) ceiling.
This method provides an accepted, easy to
apply approach, in dealing with high ceiling
applications for generalized fire conditions. It
does not, however, provide guidance for ceiling
heights over 30 feet (9.1m). In such installa-
tions, engineering judgment, the manufactur-
er’s recommendation or detector spacing
approved by the authority having jurisdiction
should be used.
In many applications, Protectowire Linear
Heat Detector is used for electrical activation
of pre-action or deluge type sprinkler sys-
tems. In sprinkler release applications, special
Factory Mutual (FM) spacing requirements
may be required. In some cases, FM spacing
requirements may conflict with the recom-
mendations for high ceilings provided in
NFPA 72. In these situations, general practice
is to utilize NFPA 72 recommendations in sys-
tems involving detection only, and to follow
FM detector spacing guidelines when design-
ing a detection system to be used for sprinkler
system release. In all cases, the final detector
spacing must be accepted and approved by
the authority having jurisdiction.
The reduction of heat detector spacing on
high ceilings as required in NFPA 72, is by no
means universally applied. Several types of
heat detectors including “line-type electrical
conductivity detectors,” more commonly
known as analog line-type detectors, have
been identified in NFPA 72 as an “exception”
to the high ceiling derating requirements.
This “exception” has been promoted on sev-
eral levels to infer that analog detectors have
been excluded from the reduced spacing
requirements due to superior performance.
In actual fact, The Fire Detection Institute Fire
Test Report, which was used as a basis for the
high ceiling derating information contained
in NFPA 72, does not include data on integra-
tion-type detectors and therefore, “exception”
was granted only until such time as data is
developed for this type of detector.
For the purposes of this manual, good system
design dictates that the listed spacing of all
installed heat detectors, regardless of operat-
ing principle, be reduced to compensate for
the effects of ceiling height.
Sloped Ceilings
In areas having a sloped or peaked ceiling, at
least one line of Protectowire must be located
at or within 3 feet (0.9 m) measured horizon-
tally from the peak, but not closer than 4 inches
(10 cm) vertically to the peak. The spacing of
additional runs of Protectowire, if any, should
be based on the horizontal distance projected
down from the ceiling and in accordance with
the type of ceiling construction.
Pre-Action Sprinkler Systems
When Protectowire Linear Heat Detector is
used as the initiating device for pre-action
sprinkler systems, special Factory Mutual loca-
tion and spacing guidelines may be found in
FM Loss Prevention Data Sheets such as 8-29,
which covers Refrigerated Storage Facilities.
As a general rule, FM acceptance criteria for open
area ceiling applications such as that
covered in 8-29, requires that the detector be
installed at a spacing not exceeding the allowable
ceiling sprinkler spacing. The detector
spacing is accomplished by maintaining a contin-
uous run of Protectowire parallel to each branch
line. At the end of each branch line the detector is
run at a right angle (maintaining the appropriate
2.5 inch [6.4 cm] bend radius) across to the next
S
2
S
S
S
2
S
2
S
2
S
2
S
2
Figure 5
DETECTOR MAY
B
E PLACED
ANYWHERE IN
T
HIS AREA,
BUT NOT CLOSER
THAN 4 INCHES
(102MM)
V
ERTICALLY TO
THE PEAK.
Comentários a estes Manuais